28
Maintenance
WARNING: To prevent personal injury,
only qualied personnel may perform
inspections and repairs to this machine.
Tank Filling
Tank Fill Adjustment
Calibration Check
Beeper Setting
Esc
Figure 14
The Setup Menu
Air Purge Info
1
2
3
4
5
6
WARNING: To prevent personal
injury while working with refrigerant,
read and follow the instructions
and warnings in this manual, and
wear protective equipment such as
goggles and gloves.
Figure 13
Lockout / Tag Out
Lever
General Maintenance
Wipeoffthemachineoftenusingacleanclothto
removegreaseanddirt.
Electrical Protection
Themachineisequippedwithacircuitbreakeronthe
controlpanelabovetheON/OFFswitch.Ifthebreaker
trips,itsbuttonwillpopout.Atrippedcircuitbreakerwill
causethemachinetoloseallpower.Pressthecircuit
breakerbuttontoreset.
Lockout / Tag Out
Toensurethatunauthorizedpersonnelcannotrunthe
machine,usetheLockout/TagOutfeature.Referto
Figure13.
1.TurntheLockout/TagOutlevercounterclockwise
(CCW).
2.Insertapadlockorotheritemthroughthealigned
holessothelevercannotbeturnedclockwise(CW)
tostartthemachine.
Tank Fill Adjustment
ThemaximumcapacityoftheISVis6.1kg(13.4lbs.).
Thisvaluemaybeadjustedtosuittheapplication.The
minimumvalueis1.8kg(4lbs.).
1.SelectTANK FILL ADJUSTMENTfromtheSetup
menu.SeeFigure14.
2.Themachinedisplaysthedefaultamountof
refrigerant:
TANKLEVEL
6.1KG
3.SelectOKtoacceptthedefaultamount,orusethe
keypadtoenteranamountandselectOK.
Garage Data