17
120001 Rev K 1-19-18
Bennett self contained dispensers can be used with aboveground tank installations if the following
requirements are met:
An Underwriters (U.L.) Listed Pressure Regulating Valve designed for under-the-pump mounting is
installed for each pumping unit according to the valve manufacturer’s instructions.
Any additional valves suggested by the Pressure Regulating Valve manufacturer are installed
according to the manufacturer’s recommendations.
The installation must be installed and used in accordance with Federal, State, Local, and National
Electrical code NFPA #70 and Motor Fuel Dispensing Facilities and Repair Garages code NFPA
30A.
Follow PEI/RP200 Recommended Practices for Installation of Aboveground Storage Systems.
Above Ground Tank Installation with Self Contained Pumps