220 Series 45
Type: normally the outputs, when activated, remain so until a deactivation command is received (Bistable), at which point
the output will revert to its standby status. If you wish the output to return to standby automatically after a set period of time,
select the option Monostable and set this time in the option Monostable Time ON next to it.
Monostable Time ON: enter a value in seconds (1 to 86400 in 1 second steps) to indicate the time for which the output,
if monostable, remains active before returning to standby.
Input
When a T1, T2, T3, T4, T5 or T6 terminal is configured as an input, it can be programmed as Normally Open or Normally
Closed (see Polarity). The input is polled at least every 30 ms and, if its state remains stable for more than 300 ms, Input 1
Event is generated (for terminal T1).
The following options are available when programming the inputs:
Panel Interconnection Present: if enabled, deactivation of the input generates the Panel Interconnection Fault
event and activating the input generates the Panel Interconnection Restore event.
Dialer Block: if enabled, activating the input blocks the communicator and deletes the queue.
Force Communication on Simulated Line: if enabled, activating the input switches from PSTN to GSM.