EasyManua.ls Logo

Bentone BF1 RME - 8.1.3 Technical Data

Bentone BF1 RME
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33 Bentone BF1
General
8.1.3 Technical data
LMO14 LMO24
Pre-ignition period:
15 s 25 s
Pre-ventilation period:
16 s 26 s
Post-ignition period:
10 s 5 s
Safety period:
< 10 s < 5 s
Re-connection after release:
< 1 s < 1 s
Reaction time flame extinction:
< 1 s < 1 s
Ambient temperature:
-5 - +60°C -5 - +60°C
Min. current with flame:
45 µA 45 µA
Max current when dark, start:
5,5 µA 5,5 µ A
Ingress Protection:
IP 40 IP 40
LOA not to be used within EU
Photocell current checks
Photocell current is measured with a direct current ammeter
(mulitimeter A) connected in series with the photocell.