8.1.3 Technical data
LMO14 LMO24
Pre-ignition period:
15 s 25 s
Pre-ventilation period:
16 s 26 s
Post-ignition period:
10 s 5 s
Safety period:
< 10 s < 5 s
Re-connection after release:
< 1 s < 1 s
Reaction time flame extinction:
< 1 s < 1 s
Ambient temperature:
-5 - +60°C -5 - +60°C
Min. current with flame:
45 µA 45 µA
Max current when dark, start:
5,5 µA 5,5 µ A
Ingress Protection:
IP 40 IP 40
LOA not to be used within EU
Photocell current checks
Photocell current is measured with a direct current ammeter
(mulitimeter A) connected in series with the photocell.