How to set closing direction and fail position
You can use the SW2 dip switches to set the closing direction (dip
switch C) and the fail position (dip switches A & B) in case of signal
loss.
This setting must be done with the power off.
Closing
direction
C
Fail
position
A
ON
OFF
ON
Clockwise
B
ON
Fail
last
Fail
closed
OFF
Countercl
ockwise
OFF
Fail
open
Fail
last