8 MANUAL OVERRIDE
In case of loss of power
supply, you can operate the
actuator manually using the
driving square under the
actuator.
This 10 mm driving square can
be driven using a suitable
wrench.
To operate the actuator using
the manual override, follow
the direction of rotation
indicated by the stickers
located on the side and below
the actuator.
AQ1L / AQ3L
side sticker
AQ7L
side sticker
!
Be careful not to damage the actuator during manual
operation.
Do not apply a torque higher than 3 Nm (AQ1L and AQ3L)
or 6 Nm (AQ7L) to the square.
Check the indicator when using the manual override to
avoid reaching the mechanical stops.