7 RE-STARTING TORQUE LIMITING DEVICE
In case of excessive torque on the actuator, a torque limitation
system shuts down the actuator.
A LED behind the switch board is lighting up when this protection is
ON.
How to re-start the actuator after an over-torque detection
Switch off the power supply.
Check if the issue comes from the valve (stiff point or jamming)
or the mechanical stops (over-travel).
Fix the issue.
Switch back on the power supply and electrically operate the
actuator in both directions.
The LED remains lit for a few seconds after the power supply
is switched off.
Wait those few seconds before switching back on the power
supply and operating the actuator.