EasyManua.ls Logo

BITMAIN AntMiner S21 Pro - Environmental Requirements; Basic Environmental Requirements; Climatic Conditions; Site Requirements of the Server Running Room

BITMAIN AntMiner S21 Pro
31 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S21 Pro User Guide
22
5 Environmental Requirements
Please ensure that your server operates in accordance with the following environmental
requirements.
5.1 Basic Environmental Requirements
5.1.1 Climatic Conditions
Table 5-1 Requirements of climatic conditions
Descriptions
Requirements
Operating Temperature, °C
-20-
45
Operating Humidity, RH
10-90%(non-condensing)
Storage Temperature, °C
-20-70
Storage Humidity, RH
10-90%(non-condensing)
Altitude, m
<2000
5.1.2 Site Requirements of the Server Running Room
Please ensure that the server operating room is kept away from industrial pollution
sources:
(1) For heavy pollution sources such as smelters and coal mines, maintain a distance
of more than 5 km.
(2) For moderate pollution sources such as chemical industries, rubber, and
electroplating industries, maintain a distance of more than 3.7 km.
(3) For light pollution sources such as food factories and leather processing factories,
maintain a distance of more than 2 km. If unavoidable, choose a site in the
perennial upwind direction of the pollution source.
Please do not set up your location within 3.7 km of the seaside or a saltwater lake. If this
is unavoidable, ensure that the structure is as airtight as possible and equipped with air
conditioning for cooling.
5.1.3 Electromagnetic Environmental Conditions
Please keep your site away from transformers, high-voltage cables, transmission lines,
and high-current equipment. For example, there should be no high-power AC
transformers (>10KA) within 20 meters, and no high-voltage power lines within 50
meters. Additionally, keep your site away from high-power radio transmitters; for
example, there should be no high-power radio transmitters (>1500W) within 100 meters.

Related product manuals