ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
32
c) Water tank replenishment: Replenish the water tank with Water filling pump P11.
d) Regular replenishment of water tank: Replenish the water tank with the Water filling pump P11 or through
the manual filling port on the top of the water tank.
1) Preparation
a) Prepare the coolant.
b) Connect the external pipeline according to the previous chapters.
c) Check if all the plugs on the automatic exhaust valves on the internal and external connecting pipelines of
the container are open (see 错误!未找到引用源。 and Figure 7-7 Schematic diagram of valve opening
and closing
d) ).
e) Open the filling valve V209 and close the drain valve V201 (see
f) Figure 7-3 Location of the exhaust valve in container system
g) and Figure 7-4 Water distributor drain port
h) ).
i) Open the exhaust ball valve V702 on the top of the water tank to ensure that the water tank is connected to
atmospheric pressure (as shown in Figure 7-12).
j) Open the manual exhaust valve V701 of the system and connect the PU pipe to the quick connector on the
water tank (to accelerate the first Water filling).