ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
9
3.3 Working Principle
Pump Station
The pump station provides two cooling Waters that meet the requirements for temperature,
pressure, flow rate, and medium to the Water distributor components. After two stages of Water
separation, the water separator delivers the cooling Water to the water-cooled plate, which takes away
the heat inside the equipment.
The heated cooling Water enters the cooling tower for forced heat exchange with the external air, or
enters a plate heat exchanger for heat exchange with the external cold source. The cooled cooling
Water is then transported to the water-cooled plate again through the pump station and water separator
components for circulation, thereby taking away the heat inside the heating load and ensuring that the
heating load operates in a good environment.
Dry Wet Tower
The dry wet tower for both dry and wet use should be used for both dry and wet working
conditions. The working principle of wet working conditions is to use water and air as cooling media,
and use the evaporation of some cooling water to carry away the heat released by the cooling Water
during the flow process inside the coil. Internally equipped with: spray device, serpentine condensing
coil, (filler heat exchange layer) dehydrator, bottom with a water collection tank, external spray pump,
and top with an axial flow fan. During operation, cooling water is pumped from the spray pump to
the upper part of the condensing disc and the Water condensed by the cooling water outside the tube
flows out from the lower part of the condensing disc. After absorbing the heat of the coolant, a portion
of the water evaporates into water vapor, which is sucked away by an axial flow fan and discharged
into the atmosphere. The non evaporative cooling water drips into the lower collection tank for
circulation by the spray pump. The axial flow fan draws air from the top, strengthening air flow,
causing the water collection tank to bear negative pressure, reducing the evaporation temperature of
water, accelerating water film evaporation, and strengthening the heat release of the condensing coil.
The function of a dehydrator is to block non evaporative water droplets in the air and allow them to
flow back to the collection tank, in order to reduce the consumption of cooling water. In addition, a
floating ball valve is also installed in the water collection tank. When the water continuously
evaporates and consumes, the floating ball valve automatically opens to provide supplementary spray
water. The working principle of dry working condition is to forcibly exchange heat between the
cooling Water with high temperature from the water-cooled plate and low-temperature air, and the