ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
11
4 ANTSPACE HK3 Container Water Cooling System Performance Index
Requirements
Table 4-1 System performance index requirements
SN
Items
Performance index
Remarks
Environment
1
Working temperature
-3540℃
Outdoor
Working temperature
540℃
Indoor (controllable
temperature range by
adjusting the fan)
2
Working humidity
1090%
3
Storage temperature
-3570℃
4
Storage humidity
595%
5
Altitude
2000m
Container technology
1
External dimensions
H)(mm
6058×2438×2896
2
High computing power
server capacity
210 S21 Hyd. series and
S19 Hyd. series high
computing servers
3
Box certification
China Classification
Society Certification
4
Safety certification
NFPA 79:2021
UL 508A:2018 R8.21
CSA C22.2 No. 14-18
ANSI/ISO 12100:2012
5
Operating power(kW)
10471050
Excluding dry wet tower
power consumption
6
Input voltage and power
AC 400V±5%,
60Hz/50Hz
7
Transport weight (T)
8
Excluding high computing
power servers and water
cooling
8
Operating weight (T)
12
Including high computing
power servers and water
cooling
9
Main switch capacity of
distribution cabinet (A)
1200
The container Water cooling
system includes two
distribution cabinets, each
with a 1200A main switch

Related product manuals