ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
35
l) After the above operation is completed, the system back pressure (pressure gauge PI03/return
pressure sensor PT02) will be stabilized at 1-1.5 bar and for normal operation. Automatic mode
can be turned on and the computing power server can be turned on for operation.
Figure 7-14 Distribution of solenoid valves in the Water filling system
Figure 7-15 Water filling system interface