ANTSPACE HK3 Water cooling container & Dry-Wet Tower Product Manual
77
7) Maintenance of Cooling Towers
After the cooling tower is put into operation, it is necessary to regularly check the operation
status and pay attention to the following points:
a) After the cooling tower enters the water, it must be strictly controlled. Damaged water pipes and
nozzles should be replaced in a timely manner to avoid affecting the water distribution effect or
damaging the water spraying device. If there are any debris, it should be removed in a timely
manner.
b) The suspended solids content of spray water is generally controlled below 20mg/L. When the
suspended solids content increases, water quality treatment agents should be appropriately added
for treatment. For long-term operation, scale inhibitors should be considered. The water quality
requirements are shown in the table below (refer to GB/T18430.1-2007). It is recommended to
replace the spray water at least twice a year, and the specific situation should be increased
according to the local water quality situation of the project.
Table 9-4 Recommended standards for spray water
Cooling Water Quality
Items
Reference value
Inclination
Corrosion
Scaling
Benchmark
items
PH (25℃)
uS/cm
6.5~8.0
O
O
Conductivity
(25℃)
<800
O
O
𝐢𝐿
βˆ’
mg(𝐢𝐿
βˆ’
)/L
<200