KT-200-2 27
y Enclosure class
- terminal box of control IP65
- terminal box of compressor IP65
- frequency inverter IP54
- High pressure switch IP54
y Minimum requirements for the use of
residual current circuit breakers
- Use a residual current circuit
breaker, type B (inverter-resistant),
sensitive to all current types, with a
nominal residual current of 100 mA
if the discharge current is to be
protected.
- Such a circuit breaker is not
suitable for personal protection.
- Additional appropriate measures
have to be taken for personal
protection!
y Compliance with the EU directive
2004/108/EC (electromagnetic
compatibility, EMC), class B1