13. Technical parameters of BPS2000 unit
No.
Item
Parameters
1 Inputs
Input voltage
110/230V/400V 50/60HZ
Maximum input load
16A/32A/3x16A/3x32A
Cable specicaon
250V/16A: 3×2.5mm
2
×3M
250V/32A: 3×6.0mm
2
×3M
400V/16A: 5×2.5mm
2
×3M
400V/32A: 5×6.0mm
2
×3M
Input plug
250V/16A: 3×2.5mm
2
×3M IEC60309 plug
250V/32A: 3×6.0mm
2
×3M IEC60309 plug
400V/16A: 5×2.5mm
2
×3M IEC60309 plug
400V/32A: 5×6.0mm
2
×3M IEC60309 plug
2 Outputs
Output voltage
230V AC
Maximum output load
10A for IEC 320 C13
16A for IEC 320 C19
Sockets standard
IEC320 C13, IEC320 C19, NF C61-314, DIN49440
Number of sockets
From 5 to 42 depending on conguraon
3 Display Hot Swap module
LCD screen displays voltage [V], load [A], power
[kW], power meter [kWh]
4 Specicaon
Dimensions L×W×H [mm]: x × 44.4 × 68
Case colour Black aluminium
5 Mounng Vercal mounng or horizontal depending on models 1U 19” or 0U
6
Temperature 0°C ÷ 60°C
Environment
Relave humidity 10% ÷ 95%