86
Migration ER11 - ER12
Functions - Comparison with ER11 versions
Function ER11 ER12 Comments, Action
Code Value Code Value
Frequency bFr 50 bFr 50 No change.
High Speed HSP 50 HSP 50 No change.
LI operation Logic - (Positive) nPL POS "Depend on LI assignment on each function (LI1 to LI4 L
or H).
See function assignment page 50
"
Integrated EMC
filter
- Yes - Yes No change.
LI assignment LI1 Forward LI1 Forward No change.
LI2 Reverse LI2 - Change rrS (COnF, FULL, Fun, rrS), LI2.
LI3 2 Preset
speed
LI3 - Change PS2 (COnF, FULL, Fun, PSS, Pr2), LI3.
LI4 4 Preset
speed
LI4 - Change PS4 (COnF, FULL, Fun, PSS, Pr4), LI4.
Speed reference SP2 10 SP2 10 No change.
SP3 25 SP3 15 Change SP3 (COnF, FULL, Fun, PSS, SP3), 25.
SP4 50 SP4 20 Change SP4 (COnF, FULL, Fun, PSS, SP4), 50.
AO assignment (dO, ACt), rFr Motor
frequency
AO1 - Change AO1 (COnF, FULL, I-O, AO1-,AO1), OFr.
AI assignment (AIt, ACt), 5U Speed ref. 5V AI1t Speed ref.
5V
No change.
Command
channel
LSr - Fr1 - No change.
SSr - FLO - No change. (possible setting on FLO & FLOC)
FLOC -
Motor parameter
choice
COS According to
rating
COS - COS is visible only if Motor parameter choice "MPC" is
set to COS.
Change MPC (COnF, FULL, drC-, MPC), COS.
Change COS (COnF, FULL, drC-, COS), According to
rating.
Motor control type unchangeable SVC Ctt STD (U/F) Change CTT (COnF, FULL, drC-, CTT), PERF (SVCU).