EasyManua.ls Logo

BLEMO ER23 - Page 40

BLEMO ER23
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40
Configuration and adjustment variables
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
11201 2052 / 2 Stt R/WS Normal stop mode
Factory setting: 0
Stop mode on disappearance of the run command or appearance of a stop command.
0 = "rMP": On ramp
1 = "FSt": Fast stop
2 = "nSt": Freewheel stop
3 = "dCI": DC injection stop
11204 2052 / 5 FSt R/WS Fast stop via logic input
Factory setting: 0
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
If LAC = L3, the following assignments are possible:
171 = "Cd11": bit 11 of the CMD control word (page 19) written by Modbus or CANopen
172 = "Cd12": bit 12 of the CMD control word (page 19) written by Modbus or CANopen
173 = "Cd13": bit 13 of the CMD control word (page 19) written by Modbus or CANopen
174 = "Cd14": bit 14 of the CMD control word (page 19) written by Modbus or CANopen
175 = "Cd15": bit 15 of the CMD control word (page 19) written by Modbus or CANopen
The stop is activated when the logic state of the input changes to 0 and the control word bit
changes to 1. The fast stop is a stop on a reduced ramp via parameter dCF. If the input falls
back to state 1 and the run command is still active, the motor will only restart if 2-wire level
control has been configured (tCC = 2C and tCt = LEL or PFO, see page 33). In other cases, a
new run command must be sent.
11230 2052 / 1F dCF R/WS Coefficient for dividing the deceleration ramp time for fast stopping
Unit: 1
Factory setting: 4
Adjustment range: 0 to 10
Parameter accessible if a fast stop has been assigned by one of the following parameters:
Stt/FSt (page 40) or EPL/OHL/OLL/SLL/COL (page 59) or LFL/StP (page 59).
Ensure that the reduced ramp is not too low in relation to the load to be stopped.
The value 0 corresponds to the minimum ramp.
11203 2052 / 4 dCI R/WS DC injection via logic input
Note This function is incompatible with the "Brake control" function (see page 14).
Factory setting: 0
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
If LAC = L3, the following assignments are possible:
171 = "Cd11": bit 11 of the CMD control word (page 19) written by Modbus or CANopen
172 = "Cd12": bit 12 of the CMD control word (page 19) written by Modbus or CANopen
173 = "Cd13": bit 13 of the CMD control word (page 19) written by Modbus or CANopen
174 = "Cd14": bit 14 of the CMD control word (page 19) written by Modbus or CANopen
175 = "Cd15": bit 15 of the CMD control word (page 19) written by Modbus or CANopen
Braking is activated when the logic state of the input or control word bit is at 1.
11210 2052 / B IdC R/W Level of DC injection braking current activated via logic input or selected as stop mode
Note: This setting is not related to the "automatic standstill DC injection" function.
Unit: 0.1 A
Factory setting: 0.7 In (1)
Adjustment range: 0 to In (1)
After 5 seconds the injection current is peak limited at 0.5 Ith if it is set at a higher value.
(1)In corresponds to the nominal drive current indicated in the Installation Manual and on the
drive rating plate.