General 1.4 Parameter change
Page 8 BOGE Operating instructions trinity
Time
1. Input code 010 as described in ‚Fundamental Procedures’ → For exam-
ple: 1 00:00:00 h, appears in the display and the left number (here ‚1’)
blinks.
2. Use arrow keys / to select the actual day (Monday = 1, Sunday = 7)
and ENTER key to change time input,
→ now the second number from
the left blinks (here ‚00’).
3. Use arrow keys / to input the actual hour (00...23) and ENTER key
to select minute (00...59), set it and then change to second selection,
set and when the set time (and set day) agrees with the actual time, press
ENTER key
→ the time is set and now the exact time display appears
as described in ,Software point 11’.
Messages
If !!!*** xx ***!!! appears on the display
(xx = blinking number), this is an error message according to the following
table:
By pressing the ENTER key , when the specific message is displayed, the
message is acknowledged and the previous display reappears – presupposed
the reason responsible for the message has been eliminated.
Parameterization codes
Num-
ber
Meaning Remedy Others
16 Pressure transmitter is defective Replace pressure transmitter
25 Balance storage Repeat software loading Replace control
32 Pressure transmitter line break Correctly connect pressure trans-
mitter (+24 V to 1)
Replace pressure transmitter or its plug
Parameter type Code Remark Page
Pressure target values 360 Highest + lowest switching point 6
Number of compressors + Interval
time
832 Set interval time to 0 h = timer operation 7
Switching times 798 All priority sequences can be set, 000 = general output lock return:
Hold arrow key and then press ENTER key at the same time
7
Timer 010 Day: 1 = Monday, 7 = Sunday 8