3.5.11 P10 Back flushing time
NOTE
This parameter is only visible with filter type P0 = 1, type 6.21/6.22/6.23/6.24.
Setting: ND 32 = 1 / ND 40 = 2 / ND 50 = 3 (ND = nominal diameter)
A certain control time is selected from a table according to the nominal diameter.
The parameter is not required if the setting is P0 1.
NOTE
For filter type 6.21/6.22, the backflushing time must generally be set to ND 50=3.
3.5.12 P11 Language
You can select from German, English, French and Spanish.
Adjustable in steps of one Range 0 to 2
Factory setting Initial setting ND 32 = 1 s
Text display, line 1 P10 flush.time
Text display, line 2 ND=XX =XX sec
Setting D German
ES Spanish
FFrench
GB English
Factory setting Initial setting D German
Text display, line 1 P11 Language
Text display, line 2 GB English