24 / 32 Operating instructions Typ 2200
Betriebsanleitung Typ 2200
Potential-free contacts and messages 6.61.07 Alarm DP
Functional description 6.61
See the operating instructions for the filter's function.
Flushing is triggered by:
Special attributes
When flushing is triggered by switching on the power and an open limit
switch, a flushing cycle starts directly with the flushing valve.
If the controller is in parameterisation mode, flushing cannot be triggered
manually.
If the "Controller type" parameter is changed, the functions are re-started.
1) "Control voltage monitoring" alarm Output A1, A2, A3
2) Collective fault, comprising: Output A4, A5, A6
- "Maximum differential pressure reached" alarm
- "Motor fault" alarm and
- "Cartridge" alarm (DP alarm flushing oil
treatment)
3) "Backflushing triggered by DP" alarm Output A7, A8, A9
1) Switching on the power supply
2) Key F
3) The forced flushing time elapsing
4) Pressure switch "DP reached, backflushing filter"