ACS 553, ACS 563 Service Manual
1 689 975 295 2021-04-13 Robert Bosch GmbH
50
Diagnostics and Testing
  

Calibrate Load Cells Calibration failed!
Slope is out of range.
󰀨
limits is too great. Select 
or  icon
Calibrate Load Cells Calibration failed!

Weight too high or low.
Select or  icon.
Calibration Check Calibration failed. Select  icon to return to the be-
ginning of the calibration check, or 
icon to return to the service menu.
Charge 󰀩
charge.

enough refrigerant. Select 
, or  icon.
Charge 󰀩
available for charge.
Refrigerant in ISV too low. Select

Charge Leak Test Leak test failed! Check for leaks and retest.
Select  icon.
Drain Oil Oil drain halted.
Pressure error.
󰀩
of separator. Select or 
icon.
Drain Oil Oil drain halted. Flow error. Oil drain timed out. Select or
 icon.
Enter Password Invalid password! Password entered is incorrect. Verify
function password is correct. Select
 or  icon.
Fast Charge Charge stalled!
Check connections and
valves. XX.XXXYY of
XX.XXXYY charged.
Check panel valve position and
couplers. Select or 
icon.
Filter Change Invalid serial number! 󰀨

previously installed. Select 
or  icon.
Filter Change Serial number has already
been used.
󰀨

previously installed. Select 
or  icon.
Helium Leak Test Transducer error. 
Leak Check Pressure test failed.
Check for leaks.
Locate and repair any leaks. Select
 or  icon.
Leak Check Vacuum test failed.
Check for leaks.
Locate and repair any leaks. Select
 or  icon.
