Planning
A fire safety analysis should be performed to determine the characteristics of the area
including a fire load calculation. The placement of the camera or cameras results from the
application environment of the customer.
Minimum distances
The camera must be mounted according to the following graphic:
d
Minimum distance to fire
h Installation height
The table below demonstrate exemplarily the minimum distances to fire or smoke depending
on the installation height:
Installation height [m]
Minimum distance to fire [m]
2.5 3.3
3 4.0
3.5 4.6
4 5.3
4.5 6.0
5 6.6
5.5 7.3
6 8.0