B B
Figure 4.1: Definition of margin areas of the picture
A
Horizontal margin area
B Vertical margin area
C Corner area
The following table shows exemplarily the deviation in percent from the maximum detection
distances at the middle of the picture:
Margin area
A B C
Opening angle of the
lens
100° 13 40 51
90° 11 33 43
60° 5 15 20
45° 3 9 12
AVIOTEC IP starlight 8000
Planning | en 23
Bosch Sicherheitssysteme GmbH Operation manual 2017.06 | 6.0 | F.01U.318.200