Further configuration (e.g. recording, DynDNS, VCA configuration, Alarm Inputs …):
Installation conditions / application
Scene illumination
Check the minimum illuminance is ≥ 7 lx o Yes o No Min. Illuminance: lx
Check the scene illumination for neon
tubes LEDs and adjust the ALC mode
(flickering)
o Checked
ALC mode set to:
Check the illuminance in the picture. Best
detection results with a maximum
dynamic factor of 5 (min to max in the
picture)
o Checked
Darkest spot: lx
Brightest spot: lx
Check camera field of view for backlights.
Minimize backlights.
o No backlights
o Number of backlights in the field of view:
Please make smoke tests close to backlights.
24/7 illumination o Yes o No
Field of view
Application fully covered as discussed
with the customer
o Yes o No
Minimum and maximum distances
calculated and documented for the
customer
o Yes o No
Obstructions in the picture taken into
account
o Yes o No
58 en | Appendices AVIOTEC IP starlight 8000