Notice!
The module reads the address switch setting only during power up. If you change the
switches after you apply power to the module, you must cycle the power to the module in
order for the new setting to be enabled.
The B426 address switch provides the value for the module's address. The figure below shows
the address switch setting for address 1. Refer to the table below for panel-specific settings.
Figure 3.3: Address switch set to address 1
Control panels
Switch
position
B426 address Bus type Function
Web-based configuration
setting
0 Configurable Any Web-based configuration
GV4 Series, B5512/B4512/
B3512
1 1 SDI2 Automation, RPS, or Reporting
GV4 Series 2 2 SDI2 Automation, RPS, or Reporting
GV4 Series, GV3 Series, GV2
Series, G Series v6.3 or
higher
3 80 SDI Automation
GV4 Series, GV3 Series, GV2
Series, G Series v6.3 or
higher
4 88 SDI Reporting or RPS
GV4 Series, GV3 Series 5 92 SDI Reporting or RPS
DS7240V2, DS7220V2, Easy
Series V3+, AMAX 2000
6 134 Option Remote programming, Reporting
DS7400Xi 7 13 Option Remote programming, Reporting
DS7400Xi
8 14 Option Reporting
FPD-7024 9 250 Option Remote programming, Reporting
Table 3.1: B426 address switch settings
Notice!
You can use web browser configuration of the module's bus address setting only when the
switch is in the ’0’ position.