In a mercantile burglar alarm system, an alarm sounding device located within the area of
greatest protection, or outside the area of greatest protection but within an area protected by
an alarm system, and that shares a common control unit with the system installed in the area
of greatest protection, is acceptable provided it is rated for inside service and alarm
conditions are transmitted to:
The dispatch location of the law enforcement agency having jurisdiction over the
protected property
or
A central station or residential monitoring station complying with the Standard for
Central-Station Alarm Services, UL 827.
Mount an inside sounding device at least 10 feet (3.05 m) above the floor or at the surface of
the ceiling. When fixed construction within the area could provide access for an intruder, the
mount the alarm sounding device at least 4 ft (1.2 m) as measured horizontally, away from the
edges of the fixed construction or at least 10 ft (3.05 m) above it so as to minimize access by
an intruder.
UL 636 - Holdup Alarm Units and System
When using control panels for hold-up operation, a hold-up point should be assigned to a
point as follows:
P## Point Type set to 24-hr, P## Point Response set to 0 (Point is constantly armed
regardless of the status of the system.)
P## Invisible Point set to Yes (Keypads do not display alarm activity from this point.)
When using Modem Format communication type, the unique point text should be set to ‘‘Hold-
Up’’, or equivalent language per the AHJ.
When using Contact ID communication type, because the Contact ID system doesn’t provide
custom text, the hold-up point should be associated as a “hold-up” point at the receiving
station. Set Area # Delay Restorals as follows:
Area # Delay Restorals = No (Restoral report is sent when point restores.)
ULC
Conduct testing monthly, with the primary de-energized.
18.6
18.7
100 en | Approved applications Control Panel
2015.07 | 12 | F.01U.287.180 Installation and System Reference Guide Bosch Security Systems, Inc.