2. Connect the control panel to the RPS computer using the Ethernet ports and a standard
Ethernet cable, and apply power to the control panel, if applicable. Within 2 minutes, the
RPS computer assigns an IP address using AutoIP.
3. In RPS, open the control panel account and click the Connect button. From the Connect
Via drop-down list select IP Direct. Click Connect. Once connected, perform the
necessary tasks, and disconnect when finished.
4. Reconnect the cable used for IP communication, if applicable.
For more information on using AutoIP, refer to AutoIP.
On-board Ethernet diagnostic LEDs
The control panel includes the following on-board LEDs to assist with troubleshooting the on-
board Ethernet connection.
1
2
ETHERNET
MODULE 1
MODULE
RELEASE
USB
ETHERNET
100BASE-T
LINK
E 1
Figure 8.1: On-board Ethernet and LEDs (B5512 shown)
Callout á…³ Description
1 á…³ 100BASE-T LED (green)
2 á…³ LINK LED (yellow)
Refer to the following tables for information on the 100BASE-T and LINK LEDs.
Flash pattern
Function
On Steady
Communicating at 100 Mb
Off
Communicating at 10 Mb.
Table 8.1: 100BASE-T LED descriptions
8.1.3
40 en | IP communications Control Panel
2015.07 | 12 | F.01U.287.180 Installation and System Reference Guide Bosch Security Systems, Inc.