D127 ______ 5 x Qty = ______ 5 x Qty = ______ 55 x Qty = ______
D129 ______ 23 x Qty = ______ 23 x Qty = ______ 25 x Qty = ______
D132A ______ 10 x Qty = ______ 10 x Qty = ______ 70 x Qty = ______
D133
4
______ x Qty = ______ x Qty = ______ x Qty = ______
D134
5
______ x Qty = ______ x Qty = ______ x Qty = ______
D185 ______ 245 x Qty = ______ 245 x Qty = ______ 300 x Qty = ______
D192G ______ 35 x Qty = ______ 35 x Qty = ______ 100 x Qty = ______
Ratings of other devices in the system that are not shown above:
____ ______ _____ x Qty = ______ ______ x Qty = ______ ____ x Qty = ______
____ ______ _____ x Qty = ______ ______ x Qty = ______ ____ x Qty = ______
____ ______ _____ x Qty = ______ ______ x Qty = ______ ____ x Qty = ______
____ ______ _____ x Qty = ______ ______ x Qty = ______ ____ x Qty = ______
Total A = ______ Total B = ______ Total C = ______
1
The In Alarm calculation for the B308 is: 20 x Qty + (16.25 x number of relays).
2
Currents listed are for the B450 only. Include plug-in device currents in calculations.
3
If using the proximity reader, add 100 mA to columns A, B, and C before calculating.
4
38 mA for each active relay.
5
Value = Minutes of alarm operation/60
Table 18.1: Current rating chart for standby battery calculations
Total B
1
Hours Total C
1
Alarm Operation
2
Contingency Total Ah
3
( ________ x 24 ) + ( ________ x 0.083) + 15% = _________
1
Refer to previous table.
2
Value = Minutes of alarm operation/60
3
Total Ah requirements must not exceed the Ah capacity of batteries:
– One D126 Battery = 7 Ah
– Two D126 Batteries = 14 Ah
– One D1218 Battery = 18 Ah
Table 18.2: General ampere-hour (Ah) calculation formula
Application Minimum Required
Standby Time (hr)
Minimum Alarm Time (min)
Residential Burglary 4 4
Proprietary Burglary 4 N/A
Central Station (Bank) 72 N/A
Central Station (Mercantile) 4 N/A
Police Station Connected (Bank) 72 30 (CUL)/15 (UL)
Police Station Connected (Mercantile) 24 30 (CUL)/15 (UL)
Local Burglary (Bank) 72 30 (CUL)/15 (UL)