1 689 975 285 2017-06-30| Robert Bosch GmbH
24 | BAT 645 | Faults & Troubleshootingen
4. Check voltage at measuring points M1 and M2 on
the power module (see sec. 5.6).
Voltage must be 230V.
If the voltage differs or is not present, the device
fuse is defective.
5. Replace power module if the voltage differs or is not
present.
5.4 Faults during charging
"Fault no.: 200"
Possible cause:
Maximum ampere-hour value exceeded
(> 120% rated capacity)
Remedy:
1. Check charging parameters and correct if necessary.
2. Check battery.
3. Charge only lead-acid batteries and lithium iron
phosphate batteries with a rated voltage of 12V or
24V.
"Fault no.: 210"
Possible cause:
Maximum charging time in charging phase 0 exceeded.
Remedy:
1. Check charging parameters and correct if necessary.
2. Check battery.
3. Charge only lead-acid batteries and lithium iron
phosphate batteries with a rated voltage of 12V or
24V.
"Fault no.: 220"
Possible cause:
Maximum charging time in charging phase 1 (constant
current) exceeded.
Remedy:
1. Check charging parameters and correct if necessary.
2. Check battery.
3. Charge only lead-acid batteries and lithium iron
phosphate batteries with a rated voltage of 12V or
24V.
"Fault no.: 230"
Possible cause:
Maximum charging time in charging phase 1 (constant
voltage) exceeded.
Remedy:
1. Check charging parameters and correct if necessary.
2. Check battery.
3. Charge only lead-acid batteries and lithium iron
phosphate batteries with a rated voltage of 12V or
24V.
"Fault no.: 290"
Possible cause:
General fault during charging.
Remedy:
1. Disconnect BAT 645 from power and restart
charging attempt with correct parameters.
2. Replace power module.
5.5 Hardware faults
"Fault no.: 300"
Possible cause:
Voltage above maximum value.
Remedy:
1. Check battery voltage. (12V or 24V).
2. Replace battery if battery voltage differs.
DANGER - Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
3. Check the voltage at the measuring points U
ist
and GNDA on the power module using the correct
battery voltage from a battery with 12V (see sec.
5.6).
The voltage must be 0.85V +/- 0.007V.
4. Check the voltage at the measuring points U
ist
and GNDA on the power module using the correct
battery voltage from a battery with 24V (see sec.
5.6).
The voltage must be 1.7V +/- 0.007V.
5. Replace power module if U
ist
is too high.
"Fault no.: 310"
Possible cause:
Voltage below minimum value.
Remedy:
1. Check battery voltage. (12V or 24V).
2. Replace battery if battery voltage differs.
DANGER - Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
3. Check the voltage at the measuring points U
ist
and GNDA on the power module using the correct
battery voltage from a battery with 12V (see sec.
5.6).
The voltage must be 0.85V +/- 0.007V.
4. Check the voltage at the measuring points U
ist
and GNDA on the power module using the correct
battery voltage from a battery with 24V (see sec.
5.6).
The voltage must be 1.7V +/- 0.007V.
5. Replace power module if U
ist
is too low.