Bosch IDS BOVA Installation Instructions
12.2016 | Bosch Thermotechnology Corp.Data subject to change
6 Refrigerant line routing
6.1 Precautions
Take precautions to prevent noise within the building structure due to
vibration transmission from the refrigerant lines. For Example:
When the refrigerant lines have to be fastened to floor joists or
other framing in a structure, use isolation type hangers.
Isolation hangers should also be used when refrigerant lines are
run in stud spaces or enclosed ceilings.
Where the refrigerant lines run through a wall or sill, they should
be insulated and isolated.
Isolate the lines from all ductwork.
Minimize the number of 90º turns.
Isolation From Joist/Rafter
Side View
8FeetMaximum
Joist/Raft er
Isolator
Line Set
8 Feet Maximum
Secure Suction li ne from joists using isolators every 8 ft. Secure
Liquid Line directly to Suction line using tape, wire, or other
approp riate method every 8 ft.
Figure 12
Isolation In Wall Spaces
Side View
Wall
Isolator
Line Set
8 Feet Maximum
Secure Suction Line using isolators every 8 ft. Secure Liquid Line
directly to Suc tion Line using tape, wire, or other approp riate
method every 8 ft.
8FeetMaximum
Figure 13
Comply with National, State, and Local Codes when isolating line sets from
joists, rafters, walls, or other structural elements.