Bosch IDS BOVA Installation Instructions
12.2016 | Bosch Thermotechnology Corp.Data subject to change
2 Unit location considerations
2.1 Unit dimensions
Unit Dimensions
Models H x W x L (Inches)
BOVA-36 24-15/16 x 29-1/8 x 29-1/8
BOVA-60 33-3/16 x 29-1/8 x 29-1/8
Table 1
The unit’s weight values is on the carton box.
When mounting the outdoor unit on a roof, be sure the roof will support the unit’s
weight. Properly selected isolation is recommended to prevent sound or vibration
transmission to the building structure.
L
H
W
Figure 1
2.2 Refrigerant piping limits
Maximum line equivalent length = 100 feet.
Maximum vertical equivalent length = 50 feet.
Use only the line diameters indicated in Table 5.1.
If the suction line sets are greater than 60 feet do not use a larger suction
line than recommended.
Standard Line
Set 100’ Max
Line Length
50’ Max
Line Lift