5 Refrigerant line considerations
5.1 Refrigerant line and service valve connection sizes
Models Suction line Liquid line
Suction line
connection
Liquid line
connection
BOVA-36 3/4 3/8 3/4 3/8
BOVA-60 7/8 3/8 7/8 3/8
Table 2
5.2 Required refrigerant line length
Determine required line length (Fig. 9).
Line Length
Figure 9
5.3 Refrigerant line insulation
The Suction Line must always be insulated. DO NOT allow the Liquid Line
and Suction Line to come in direct (metal to metal) contact.
Suction Line
Liquid Line
Insulation
Figure 10
5.4 Reuse existing refrigerant lines
CAUTION:
If using existing refrigerant lines make certain that all joints
are brazed, not soldered.
For retrofi t applications, where the existing refrigerant lines will be used, the
following precautions should be taken:
Ensure that the refrigerant lines are the correct size. Refer to Section 5.1
listed and Table 2.
Ensure that the refrigerant lines are free of leaks, acid, and oil.
The manufacturer recommends installing only approved matched indoor
and outdoor systems. All of the manufacturer’s split systems are A.H.R.I.
rated only with TXV indoor systems. Some of the benefi ts of installing
approved matched indoor and outdoor split systems are maximum
effi ciency, optimum per-formance and the best overall system reliability.
Figure 11