EasyManua.ls Logo

Bosch Climate Class 6100i Series - Commissioning; Commissioning checklist; Functional test of device; Handover to the user

Bosch Climate Class 6100i Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
7
Climate Class 6100i/8100i – 6721831491 (2020/11)
4 Commissioning
4.1 Commissioning checklist
Table 8
4.2 Functional test of device
The system can be tested once the installation including tightness test
has been carried out and the electrical connection has been established:
Connect the power supply.
Switch on indoor unit with the remote control.
▶Hold the ON/OFF [1] key pressed for 5 seconds to set the Cooling
mode ( Fig. 20)
A beep sounds and the ON indicator flashes.
Test cooling mode for 5 minutes.
Ensure freedom of movement of air baffle [2].
Select the heating mode on the remote control.
Test heating mode for 5 minutes.
Press the ON/OFF key again to stop the operation.
4.3 Handover to the user
When the system has been set up, hand over the installation manual
to the customer.
Explain to the customer how to use the system, referring to the
operation manual.
Advise the customer to carefully read the operation manual.
5Troubleshooting
5.1 Faults with indication
WARNING
Risk to life from electric shock!
Touching live electrical parts can cause an electric shock.
Before working on electrical parts, disconnect all phases of the
power supply (fuse/circuit breaker) and lock the isolator switch to
prevent unintentional reconnection.
A fault on the device can also be indicated by the sequential flashing of
the following lights:
ON indicator K (green)
Timer lamp (orange)
Plasmacluster lamp (blue)
The number of flashing signs specify the number of the fault codes.
For example in case of error 23 – 4 the green lamp flashes 2 times, then
the orange lamp flashes 3 times then the blue lamp flashes 4 times. As
an alternative, the fault code called up via the remote control
operating instructions.
If a fault is present for more than 10 minutes:
Briefly interrupt the power supply and switch the indoor unit back on.
If a fault persists:
Call customer service about the fault, providing details of the fault
code and appliance.
Table 9
1 Outdoor unit and indoor unit are correctly installed.
2 Pipes are correctly
•connected,
thermally insulated,
and checked for tightness.
3 Condensate pipes are functioning correctly and
have been tested.
4 Electrical connection has been correctly
established.
Power supply is in the normal range
Protective conductor is properly attached
Connection cable is securely attached to the
terminal strip
5 All covers are fitted and secured.
6 The horizontal louver of the indoor unit is fitted
correctly and the actuator is engaged.
Fault code Possible Cause
00 – 0 Normal Operation
01 – ... Short circuit on the thermistor of the outdoor unit
02 – ... Fault caused by the temperature in the compressor or heat exchanger being too high
03 – 0 For protection, the outdoor unit is switched off for a short time.
05 – ... Open electric circuit on the thermistor of the outdoor unit
06 – ...
07 – ...
Overloading from insufficient refrigerant or blocked air inlet/outlet. Fault at IPM module or overcurrent protection of the
outdoor unit main PCB.
09 – ... Fault at thermistor or 4-way valve or insufficient refrigerant.
10 – ... Faulty parameter in the EEPROM of the outdoor unit
11 – ... Fault on fan in outdoor unit
13 – ... Fault on compressor at start or operation
14 – ... Fault at the impulse amplitude modulation
17 – ... Incorrect electrical connection of the device with open electric circuit
18 – ... Incorrect electrical connection of the device with short circuit
19 – ... Fault on fan of the indoor unit
20 – ... Faulty parameter in the EEPROM of the indoor unit
24 – ... Communication error of the indoor unit with the WLAN
26 – ... Fault on a thermistor of the indoor unit

Table of Contents

Related product manuals