Technical information
19
Compress 7400i AW – 6721833372 (2021/09)
9 Technical information
9.1 Specifications – heat pump (alternating current)
Table 10 Specifications – heat pump (alternating current)
Unit 5 OR 7 OR
Air/water operation
Power output with A -10/W35
1)
, 100% compressor speed kW 4.76 6.20
Power output with A -7/W35
1)
, partial load kW 4.24 5.66
COP with A -7/W35
1)
, partial load 3.02 3.08
Modulation range with A -7/W35
1)
kW 1.5-5.0 1.9-6.8
Power output with A +2/W35
1)
, 100% compressor speed
1) Performance data in accordance with EN 14511
kW 5.48 7.29
Power output with A +2/W35 , partial load kW 2.53 2.54
COP with A +2/W35 , partial load 4.25 4.25
Modulation range with A +2/W35 kW 1.9-5.5 2.5-7.3
Power output with A +7/W35
1)
, partial load kW 2.82 4.01
COP with A +7/W35
1)
, partial load 5.01 5.01
Modulation range with A +7/W35
1)
kW 2.1-7.6 4.0-7.9
Cooling capacity with A 35/W7
1)
kW 4.44 5.66
EER with A 35/W7
1)
2.42 2.36
Cooling capacity with A 35/W18
1)
kW 6.15 7.39
EER with A 35/W18
1)
2.98 2.86
Electrical details
Power supply 230 V 1N AC 50 Hz 230 V 1N AC 50 Hz
Protection index IP X4 IP X4
Fuse rating for supplying the heat pump directly via the building connection
2)
2) Fuse class gL/C
A 16 16
Maximum power consumption kW 3.2 3.6
Heat transfer medium
Minimum flow l/s 0.33 0.43
Internal pressure reduction kPa 7.8 10.5
Air and noise generation
Max. fan motor output (DC transformer) W 240 240
Maximum air current m³/h 3400 3400
Sound pressure level with a clearance of 1 m, load point according to 2013/811/EU dB(A) 42 42
Sound Power
3)
3) Sound power level in accordance with EN 12102
dB(A) 50 50
Max. sound power A7/W55 dB(A) 54 55
Max. sound power "quiet operation" A7/W55 dB(A) 49 51
Max. sound power A7/W35 dB(A) 55 55
Max. sound power "quiet operation" A7/W35 dB(A) 47 48
Max. sound power incl. tonality dB(A) 53 + 3
4)
4) Tonality
55 + 3
4)
Max. sound power incl. tonality "quiet operation" dB(A) 49 + 0
4)
51 + 0
4)
General details
Refrigerant
5)
5) GWP100 = 2088
R410A R410A
Refrigerant charge kg 1.75 2.35
CO
2
(e) Tonne 3.65 4.91
Maximum temperature of flow, heat pump only °C 62 62
Installation altitude above sea level up to 2000 m above sea level
Dimensions (W x H x D) mm 940x1380x600 940x1380x600
Weight without walls and top cover kg 89 96
Weight with walls and top cover kg 113 120