Installation
15
Condens 7000 F – 6720871560 (2019/11)
5 Installation
5.1 Installation location requirements
DANGER:
Risk of fire through flammable materials or liquids.
Never store flammable materials or liquids in the immediate vicinity
of the boiler.
NOTICE:
Risk of material damage due to contaminated combustion air!
Do not use cleaning agents that contain chlorine or halogenated
hydrocarbons (e.g. in spray cans, solvents and cleaning agents,
paints and adhesives).
Do not store or use these substances in the boiler room.
Keep the combustion air supply free of dust or use the “air filter”
accessory set.
NOTICE:
Material damage due to overheating!
Excessive ambient temperatures can result in heating system damage.
Ensure the ambient temperature is above 0 °C and below 35 °C.
NOTICE:
Frost damage!
Install the heating system in a frost-free room.
5.2 Preventing noise disturbance for end-users
Where the boiler surroundings are sensitive to noise (e.g. residential
units), use the silencer options offered by the manufacturer
(flue gas silencer, expansion joints).
5.3 Wall clearances
When determining the installation location, take the clearances for the
flue gas routing and the connection pipe assembly into consideration
( Fig. 10).
Where applicable, allow extra wall clearances for additional
components, for example DHW cylinder, pipe connections or other
components on the flue gas side.
Fig. 10 Wall clearances at the installation location (right-hand version)
Fig. 11 Wall clearances at the installation location (left-hand version)
Table 5 Recommended and minimum wall clearances
Wall clearance [mm]
Dimension minimum recommended
A 600 1000
B 100 400
C
1)
1) This clearance depends on the flue system installed.
––
D 800 1000
E
1)
150 400
0010012544-001