Inspection and maintenance
Condens 7000 F – 6720871560 (2019/11)
34
11.4.2 Carrying out gas tightness test
Turn off appliance shut-off valve.
Undo locking screw on test nipple by turning it through 2 revolutions.
Push the test hose of the U-tube pressure gauge onto the test nipple.
Open the fuel shut-off valve and wait for the pressure to stabilise.
Note and record the pressure.
Close the appliance shut-off valve and check the pressure again a
minute later.
Calculate the pressure drop per minute from the differential.
By means of the determined pressure drop per minute and the test
volume (V
test
), check in the following diagram ( Fig. 37, page 34)
whether the gas train is still useable.
Fig. 36 Testing the gas supply pressure
[1] Test nipple for measuring the gas supply pressure and for venting
Fig. 37 Permissible pressure drop per minute for the internal leak test with gas pressure present
[1] “Valve tight” range = applies to new installations
[2] “Valve sufficiently tight” range = valve can be used without
restrictions
[3] “Valve leaks” range = valve may not be used
(perform a test as described in the following)
x Test volume in litres
y Pressure drop in mbar within one minute
Read-off example: test volume (V
test
) 5 litres and pressure drop
4 mbar/min = range 3 (valve leaking = valve may not be used)
carry out test as described below.
If you detect a steep pressure drop of > 10 mbar/minute at a test volume
of (V
test
) of < 1 litre, increase the test volume (V
test
). For this include the
pipework up to the next shut-off valve in the tightness test and repeat the
test using the new test volume (V
test
).
If the read-off point for the test volume (Vtest) and pressure drop per
minute lies within the "Train leaks" range (see Read-off example), you
must carry out the test described below.
NOTICE:
Risk of material damage due to a short circuit!
Never spray or let leak detection agent drip onto cable entries, plugs
or electrical cables/leads.
Cover areas at risk before testing for leaks.
Check all joints in the tested pipework section using a foaming leak
detection agent.
If required, seal any leaks and repeat the test.
If no leak is detected, replace the air/gas ratio control valve.
Complete the leak test
Remove hose.
After completing the measurements, retighten the locking screw of
the test nipple.
Check tightness of the test nipples.