Operation
Condens 7000 WP – 6721842519 (2022/03)
30
Table 11 Settings menu
Menu Function check
Table 12 Menu Function check
Summer mode 0 ... 16 ... 30 °C This is only displayed if the control unit was activated.
This can be used to set the outside temperature threshold
at which the heating system switches to summer mode.
Frost prot. Yes
•No
Frost temp. limit 0 ... 5 … 10 °C Temperature value for the system frost protection.
This service function is only available if the frost
protection function was activated. If the outside
temperature does not exceed the frost threshold
temperature, then the heating pump in the heating circuit
switches on.
1) With heating controller
Meu item Settings/adjustment range Remark/restriction
Activate test
Burner Off ...100 % This service function enables you to test the burner by
adjusting the appliance output.
Ignition On
Off
Permanent ignition.
Testing the ignition by means of permanent ignition
without gas supply.
To prevent damage to the ignition transformer: leave
the function switched on for a maximum of 2 minutes.
Fan •On
Off
Permanent ignition.
Fan running without gas supply or ignition.
Pump On
Off
Permanent pump run (internal or external pumps).
Cyl. prim. pump •On
Off
Permanent pump operation of cylinder primary pump
3-way valve Heating
Hot water
Permanent position of the 3-way valve.
HC1 pump •On
Off
Permanent HC1 pumpoperation (downstream of low loss
header), if HC1 pump is installed.
DHW circ. pump On
Off
Permanent DHW circulation pump.
Ionisat.oscill. •On
Off
Check the ionisation measurement function at the flame.
Meu item Settings/adjustment range Remark/restriction