Inspection and maintenance
Condens 7000 WP – 6721842519 (2022/03)
34
Where required, clean the condensation catch pan with water.
Fig. 38 Open the cover of the condensation catch pan.
10.7 Cleaning the siphon
Remove the flexible hose, and possibly the tee, from the siphon.
Unscrew the union nut of the siphon in the boiler and completely
screw open [1].
Remove siphon [2].
Fig. 39 Remove the boiler siphon
▶Flush the siphon.
Fill the siphon completely with water.
Reattach the siphon.
Check whether the neck of the siphon is properly connected to the
condensation catch pan.
Tighten the union nut hand tight.
10.8 Installing the gas-air unit.
Clean the contact surfaces of the heat exchanger.
Reinsert the burner back into the heat exchanger
When reinserting, observe the position of the centring axis [1].
Tighten the screws (3 Nm) [2].
Fig. 40 Installing of the burner
Install the new burner gasket [1].
Position the gas-air mixing pipe.
Tighten the nuts on the gas-air mixing pipe (17 Nm) [2].
Fig. 41 Installing the gas-air mixing pipe
Connect the plug on the fan.
Install the air collector [1].
0010040896-001
1.
2.
0010040938-001
2.
1.
0010040886-001
1
23 Nm
0010040884-001
1
217 Nm