Inspection and maintenance
35
Condens 7000 WP – 6721842519 (2022/03)
Check if the pressure compensation hose [2] is connected correctly
with the gas valve and air collector.
Fig. 42 Check the connections of the pressure compensation hose
Install the gas hose.
Fig. 43 Installing the gas hose
10.9 Measure the heat exchanger air resistance [R
x
]
By measuring the air resistance [R
x
], it can be determined if the heat
exchanger has been sufficiently cleaned. For this purpose, the
measurement is compared with the measurement of the initial
commissioning. [R
0
] ( § 10.18, p. 38).
10.9.1 Preparation
To ensure a correct measurement, remove the soiling that has been
released during cleaning as well as the remaining rinsing water by
temporarily putting the boiler into operation.
Make sure that the boiler can release its heat to the system.
Open the menu Function check > Burner.
Start the Function check by setting the value to at least 50 %.
Run the appliance 2 to 3 minutes.
Deactivate Function check.
Switch off the appliance.
10.9.2 Measure the air resistance [R
x
]
Remove the cover of the condensation catch pan ( § 38, p. 34).
Open the gas/air ratio test port by turning the adjusting screw
through 2 revolutions ( § 8.3, p. 22).
Set the pressure gauge to“0”.
Connect the pressure gauge to the gas/air ratio test port.
Operate the appliance.
Open the menu Function check > Fan.
Start the Function check.
Now the fan is switched on. The burner remains switched off during
this function check.
The air resistance is read-off in Pascal [Pa].
Attention! During the measurement, the air resistance is displayed
as negative value.
▶Stop the Function check.
Close the gas/air ratio test port.
Reattach the cover of the condensation catch pan.
10.9.3 Assess the air resistance [R
]
For the assessment of the air resistance above the heat exchanger, the
following applies: R
0
- R
x
= R
The maximum decrease in the air resistance [R
] differs depending on
the product type, and must not be exceeded.
Table 16 Maximum decrease of the air resistance depending on the
product type
Example 1: with an GC7000WP 145, an air resistance was measured
during commissioning [R
0
]= -2083. The resistance measurement is
carried out during the third maintenance visit [R
3
]. According to the
calculation, the difference was less than 500 Pa.
Table 17 Example 1: assessment of the air resistance at R
3
Make a note of the value in the maintenance protocol ( § 10.18, p.
38).
Example 2: with an GC7000WP 145, an air resistance was measured
during commissioning [R
0
]= -2083. The resistance measurement is
carried out during the fifth maintenance visit [R
5
]. According to the
calculation, the difference was more than 500 Pa.
Table 18 Example 2: assessment of the air resistance at R
5
This could be caused by:
Flue gas check valve clogged.
The pollution degree in the heat exchanger is too high.
Check the flue gas check valve for defects ( § 10.16.3, p. 37)
Clean the heat exchanger again ( § 10.5, p. 33).
If the air resistance is still high: contact the Boschcustomer services.
0010041396-001
2
2
1.
0010040892-001
Product type Max. R
GC7000WP 125 400 Pa
GC7000WP 145 500 Pa
R
0
R
3
R
Action
-2083 -1857 226 No action required
R
0
R
5
R
Action
-2083 -1519 564 Find out and eliminate
the cause for the high
value.