64 en | Appendices AVIOTEC IP starlight 8000
2019.01 | 10 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH
Further configuration (e.g. recording, DynDNS, VCA configuration, Alarm Inputs …):
Installation conditions / application
Scene illumination
Check the minimum illuminance is ≥ 7 lx oYesoNo Min. Illuminance:lx
Check the scene illumination for neon
tubes LEDs and adjust the ALC mode
(flickering)
oChecked
ALC mode set to:
Check the illuminance in the picture. Best
detection results with a maximum
dynamic factor of 5 (min to max in the
picture)
oChecked
Darkest spot:lx
Brightest spot:lx
Check camera field of view for backlights.
Minimize backlights.
o No backlights
oNumber of backlights in the field of view:
Please make smoke tests close to backlights.
24/7 illumination oYesoNo
Field of view
Application fully covered as discussed
with the customer
oYesoNo
Minimum and maximum distances
calculated and documented for the
customer
oYesoNo
Obstructions in the picture taken into
account
oYesoNo