24 en | Planning AVIOTEC IP starlight 8000
2019.01 | 10 | F.01U.318.200 Operation manual Bosch Sicherheitssysteme GmbH
Influencing factor Countermeasure Information
VIBRATIONS Only mount the camera in
vibration isolated areas.
Vibrations can move and
shake the camera and result
in false alarms.
4.2 Minimum distances
The camera must be mounted according to the following graphic:
d Minimum distance to fire
h Installation height
The table below demonstrate exemplarily the minimum distances to fire or smoke depending
on the installation height:
Installation height [m] Minimum distance to fire [m]
2.5 3.3
3 4.0
3.5 4.6
4 5.3
4.5 6.0
5 6.6
5.5 7.3