Fan Motor Options | 31LV Heat Pump Series
8 733 905 683 (2016/09)LV Heat Pump Series
Table 9: Constant Airflow Motor Performance Table
Model
Fan Speed
Rated
Airflow 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
LV-015
A - Low 450 450 450 450 450 450 450 440 440 430 - -
A - Normal 500 500 500 500 500 500 500 500 480 470 460 - -
A - Hi 580 580 580 580 580 580 580 570 560 550 - -
LV-018
B - Low 550 540 540 540 540 540 540 530 520 500 - -
B - Normal 650 650 650 650 650 650 650 640 630 610 590 - -
B - Hi 750 750 750 750 750 750 740 730 710 690 - -
LV-024
C - Low 720 720 720 720 720 720 720 700 650 560 - -
C - Normal 850 850 850 850 850 850 850 850 850 800 700 - -
C - Hi
960 960 960 960 960 960 960 960 880 790 - -
LV-030
D - Low 810 810 810 810 810 810 810 770 720 650 - -
D - Normal 950 950 950 950 950 950 950 950 900 850 780 - -
D - Hi 980 980 980 980 980 980 980 950 900 820 - -
LV-036
A - Low 1020 1020 1020 1020 1020 1020 1000 990 960 930 - -
A - Normal 1200 1200 1200 1200 1200 1200 1200 1180 1160 1130 1090 - -
A - Hi 1380 1380 1380 1380 1380 1380 1360 1330 1300 1250 - -
LV-041
A - Low 1100 1100 1100 1100 1100 1090 1070 1050 1020 990 - -
A - Normal 1300 1280 1280 1280 1280 1280 1260 1240 1220 1180 1140 - -
A - Hi 1300 1300 1300 1300 1300 1280 1260 1240 1200 1160 - -
LV-042
B - Low 1190 1190 1190 1190 1190 1190 1190 1190 1190 1190 1190 -
B - Normal 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400 1400- -
B - Hi 1630 1630 1630 1630 1630 1630 1630 1630 1630 1630 1630 -
LV-048
A - Low 1340 1340 1340 1340 1340 1340 1340 1340 1340 1340 1340 -
A - Normal 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 -
A - Hi
1810 1810 1810 1810 1810 1810 1810 1810 1810 1810 1810 -
LV-060
A - Low
1700 1700 1700 1700 1700 1700 1700 1700 1690 1690 1680 -
A - Normal
2000 2000 2000 2000 2000 2000 2000 2000 2000 1980 1980 1980 -
A - Hi 2220 2220 2220 2220 2220 2220 2220 2220 2130 2100 2070 -
LV-070
B - Low 1870 1870 1870 1870 1870 1870 1870 1870 1870 1870 1870 -
B - Normal 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 -
B - Hi
2330 2330 2330 2330 2330 2330 2330 2330 2330 2330 2330 -
Note: Air flow is 70% of tabulated values during
fan only operation. Air flow is 80% of tabulated
value during passive dehumidification mode
when enabled.