7.2 Power Supply
7.2.1 External Supply Voltages
General Information
TheIndraControl L10
as well as any connected function modules and I/O as‐
semblies are supplied with power via the black terminal strip to the right of the
IndraControl L10.
Slot 4:
Fig.7-2: Supply voltage connections
Observe the color-coding of the connectors.
To connect the operating voltages only the power connector inclu‐
ded in the
connector set R-IB IL CML S01-PLSET available for the
IndraControl L10 is allowed is allowed. Connector R-IB IL SCN-
PWR IN-CP available for other power terminals is not permitted for
the IndraControl L10 .
This voltage module (PWR IN) is used to feed the following three voltages:
U
LS
(24 V
power supply), U
S
(24 V segment supply) and U
M
(24 V main supply):
Terminal
Signal
1.1 +24 VDC segment voltage U
S
).
1.2 +24 VDC supply voltage U
LS
is present.
1.3 LGND (ground supply voltage)
1.4 and 2.4 FE (functional earth ground)
2.1 and 2.2 +24 VDC supply voltage U
M
is present.
2.3 PGND (ground main and segment voltages)
Fig.7-3: Pin assignment of the voltage module
Five light-emitting diodes are arranged at the upper edge. They have the fol‐
lowing meaning:
24/54 Bosch Rexroth AG | Electric Drives
and Controls
Rexroth IndraControl L10 | Project Planning Manual
Connections and Interfaces
PWR IN