8 digital inputs 4 digital outputs
Byte-bit
view
Byte IX0.0 – 0.7 (default) QX0.0 – 0.3 (default)
Bit 0 1 2 3 4 5 6 7 0 1 2 3
Module Terminal point (signal) 1.1 2.1 1.4 2.4 1.1 2.1 1.4 2.4 1.1 2.1 1.4 2.4
Terminal point (24 V) 1.2 2.2 1.3 2.3 1.2 2.2 1.3 2.3 - - - -
Terminal point (last ground) - - - - - - - - 1.2 2.2 1.3 2.3
Fig.7-12: Address assignment of inputs and outputs
7.3.2 Digital On-board Inputs
The left-hand section of the connector panel provides 8 digital inputs as on‐
board inputs.
Slots 1 and 2:
Fig.7-13: Digital inputs
Observe the color-coding of the connectors.
Number of inputs 8
Connection method 2-wire connection
Electrical isolation to U
S
No
Electrical isolation to U
L
Yes
Reverse voltage protection Yes
Input voltage:
Nominal value for
"0"
Nominal value for
"1"
-3 V ... + 5 V ...
11 V ... 30 V
Project Planning Manual | Rexroth IndraControl L10 Electric Drives
and Controls
| Bosch Rexroth AG 29/54
Connections and Interfaces
Courtesy of CMA/Flodyne/Hydradyne Motion Control Hydraulic Pneumatic Electrical Mechanical (800) 426-5480 www.cmafh.com

Table of Contents

Related product manuals