Input current:
Nominal value for "0"
Nominal value for "1"
< 2.5 mA
2.8 mA ... 6 mA
Delay time:
for "0" after "1"
for "1" after "0"
Type 50 μs
Type 50 μs
Current consumption by 24 V supply (U
S
) Typ. 60 mA
Cable length (unshielded) < 100 m
Interrupt inputs 8
Sensor supply From U
S
via a PTC
fuse
Output voltage Type Uext. – 1 V
Nominal current (total) 0.2 A
Short-circuit protection, overcurrent protection Typ. 0.6 A
Criteria for connecting 2-wire proximity switches:
Quiescent current
Voltage drop
< 2.5 mA
< 6 V
Fig.7-14: Data of digital inputs
Light-emitting diodes indicating the current state of the inputs are arranged on
the top of the input terminals.
LEDs 1, 2, 3, 4
Meaning
Off The assigned input is not set.
Yellow The assigned input is set.
Fig.7-15: Status LEDs of digital inputs
An additional two-color light-emitting diode (identified by D) emits green light in
case the 24 V voltage is present and red light in case of a short-circuit or over‐
load.
Light-emitting diode
D
Meaning
Off 24 V voltage is missing.
Green 24 V voltage is present.
Red Short-circuit or overload.
Fig.7-16: Light-emitting diode D
7.3.3 Digital Outputs
Two terminal strips with a total of 4 digital outputs are arranged between the
digital inputs and the terminals for the voltage supply.
Slots 3:
30/54 Bosch Rexroth AG | Electric Drives
and Controls
Rexroth IndraControl L10 | Project Planning Manual
Connections and Interfaces
Courtesy of CMA/Flodyne/Hydradyne ▪ Motion Control ▪ Hydraulic ▪ Pneumatic ▪ Electrical ▪ Mechanical ▪ (800) 426-5480 ▪ www.cmafh.com