EasyManua.ls Logo

Bosch SM036 - User Manual

Bosch SM036
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Installation, Operation and Maintenance Manual
SM Series Heat pump
6 720 220 406 (2015/02)
SM024 | SM036 | SM048 | SMO60 | SM070

Table of Contents

Other manuals for Bosch SM036

Questions and Answers

  • E
    emitchellSep 13, 2025
    What to do if my Bosch SM036 Heat Pump unit turns off on high pressure control?
    • D
      Daniel JohnsonSep 13, 2025
      If your Bosch Heat Pump is turning off due to the high-pressure control, the discharge pressure might be too high. In 'COOLING' mode, this could be due to a lack of or inadequate water flow, the entering water temperature being too warm, or a scaled or plugged condenser. In 'HEATING' mode, it could be due to a lack of or inadequate airflow, an inoperative blower, or clogged filters or restrictions in the ductwork. Another cause might be that the unit is overcharged with refrigerant, requiring you to reclaim refrigerant, evacuate, and recharge with the factory-recommended charge. Finally, check for a defective or improperly calibrated high-pressure switch.
  • J
    Jerry SmithAug 25, 2025
    Why is my Bosch SM036 Heat Pump not cooling or heating enough?
    • F
      fschroederAug 25, 2025
      There are several potential reasons why your Bosch Heat Pump might not be providing sufficient cooling or heating. It could be due to an undersized unit (in which case, recalculating heating and cooling loads and adding insulation or shading might help), loss of conditioned air through leaks in ductwork or around doors/windows, inadequate airflow (check and replace the filter if dirty), low refrigerant charge, a defective compressor or reversing valve, operating pressures that don't match the unit's pressure/temperature chart, a restricted or defective TXV, or contamination of the refrigerant system with moisture or noncondensables (in which case you need to reclaim refrigerant, replace the filter dryer, evacuate the system, and recharge with the recommended charge).
  • A
    amy26Aug 25, 2025
    What to do if my Bosch SM036 compressor isn't working?
    • J
      Julie CoxAug 26, 2025
      If the compressor on your Bosch Heat Pump isn't operating but the fan is running, it could be due to an open compressor overload. Check for supply voltage at the load side of the contactor. For 3-phase models, check the phase rotation and voltage at all 3 phases. Poor wiring connections can also cause this; look for signs of heat on the wiring insulation and ensure that all wiring connections are secure and properly torqued. A burned-out compressor is another possibility; check if the compressor hums when power is applied. If not, check the resistance of the compressor windings using the values shown in the compressor characteristics chart, ensuring the compressor is cool (70° F) when checking the windings.
  • J
    John LeeDec 1, 2025
    Why is my Bosch SM036 Heat Pump providing insufficient cooling or heating?
    • B
      Benjamin WhiteDec 1, 2025
      If your Bosch Heat Pump isn't providing enough cooling or heating, several factors could be at play. First, ensure adequate airflow and proper air distribution, and replace any dirty filters. Check for leaks in the ductwork or ambient air entering through doors or windows. If the unit is undersized, recalculate the heating or cooling loads; adding insulation and shading might help. A low refrigerant charge can also cause inefficient operation, so check that. Other potential causes include a defective compressor (check if the discharge is too low and suction pressure is too high), a defective reversing valve, or a restricted or defective TXV. Compare unit operating pressures to the unit's pressure/temperature chart. Lastly, the refrigerant system may be contaminated with moisture or noncond...
  • Q
    qkramerSep 14, 2025
    What causes a Bosch SM036 Heat Pump unit to turn off on low pressure control?
    • M
      Michael ButlerSep 14, 2025
      If your Bosch Heat Pump is turning off due to the low-pressure control, it may be due to suction pressure being too low. In 'COOLING' mode, this can result from a lack of or inadequate airflow, the entering air temperature being too cold, an inoperative blower, clogged filters, or restrictions in the ductwork. In 'HEATING' mode, it may be due to a lack of or inadequate water flow, the entering water temperature being too cold, or a scaled or plugged condenser. Another cause could be the unit being low on refrigerant, requiring a check for leaks, repair, evacuation, and recharge with the factory-recommended charge. Lastly, check for a defective or improperly calibrated low-pressure switch.
  • P
    Phillip MeyerSep 18, 2025
    Why does my Bosch SM036 Heat Pump keep short cycling?
    • J
      John BarnesSep 19, 2025
      If your Bosch Heat Pump is short cycling, it might be oversized; recalculate the heating and cooling loads. The thermostat could be installed near a supply air grill; relocate it. Readjust the heat anticipator. Check for a defective or improperly calibrated low-pressure switch.
  • M
    Marcus MckaySep 8, 2025
    What to do if my Bosch Heat Pump unit shuts off due to high pressure?
    • A
      Amy RodgersSep 8, 2025
      If your Bosch Heat Pump shuts off on high pressure control, it could be due to several reasons. In cooling mode, it could be due to a lack of or inadequate water flow, entering water temperature being too warm, or a scaled or plugged condenser. In heating mode, it may be caused by a lack of or inadequate air flow, an inoperative blower, a clogged filter, or restrictions in the duct work. The unit might also be overcharged with refrigerant, requiring you to reclaim refrigerant, evacuate, and recharge with the factory-recommended charge. Finally, check for a defective or improperly calibrated high-pressure switch.
  • J
    Julie Taylor PhDSep 8, 2025
    What to do if my Bosch SM036 Heat Pump is short cycling?
    • T
      Tonya CampbellSep 8, 2025
      If your Bosch Heat Pump is short cycling, several factors could be responsible. The unit might be oversized, requiring a recalculation of heating and cooling loads. The thermostat could be installed near a supply air grill, necessitating relocation, or the heat anticipator may need readjustment. Additionally, check for a defective or improperly calibrated low-pressure switch.
  • M
    Mark RiveraDec 1, 2025
    What to do if my Bosch Air Handler unit does not run?
    • T
      Todd HernandezDec 1, 2025
      If your Bosch Air Handler unit isn't running, there are several potential causes: * **Power Supply:** Ensure the disconnect is closed and power is applied. * **Blown Fuse/Tripped Breaker:** Replace any blown fuses or reset tripped circuit breakers, ensuring fuses are the correct size. * **Low Voltage Supply:** If the voltage is below the minimum specified on the unit's data plate, contact your local power company. * **Thermostat:** Set the fan to 'ON' to see if the fan runs. Set the thermostat to 'COOL' with the lowest temperature, the unit should run in cooling mode. Set it to 'HEAT' with the highest temperature; the unit should run in heating mode. If nothing happens, the thermostat might be miswired or faulty. Check for 24 volts between 'R' and 'C,' 'Y' and 'C,' and 'O' and 'C'...
  • D
    Dennis PorterSep 2, 2025
    Why is my Bosch Heat Pump blowing warm air in cooling mode?
    • J
      Jessica CarterSep 2, 2025
      If your Bosch Heat Pump is providing excessively warm air in cooling or excessively cool air in heating, several factors could be responsible. The airflow might be too high; consult the blower performance table and reduce fan speed if possible. High or low water temperature could also be a cause; check the unit's capacity versus the water temperature. Air leakage in the ductwork can also lead to this issue, so inspect the ductwork. Finally, a loss of refrigeration capacity could be the reason; in that case, check refrigerant pressures with a gauge set.

Summary

Key to Symbols

Safety Warnings

Crucial safety precautions for installation and servicing of the heat pump equipment.

Model Nomenclature

General Description

Factory Installed Options

Lists available options like HGRH, Electric Heat, and HRP.

Moving and Storage

Initial Inspection

Location

Configurability

Horizontal Configurability

Instructions for reconfiguring the blower orientation on horizontal units.

Counter-Flow Configurability

Vertical Configurability

Access to Internal Components

Steps required to gain access to the unit's internal parts.

Return and Discharge Duct Flanges

Pre Installation Unit Preparation

Corner Cap Installation

Instructions for applying corner caps to the unit cabinet.

Mounting Vertical Units

Mounting Horizontal Units

Hanging Bracket Kit

Condensate Drain

Duct System

Piping

Water Quality

Electrical

Safety Devices and UPM Controller

Explains safety controls and the Unit Protection Module.

Freeze Sensor

ECM Interface Board

Thermostat Outputs

Lists terminal functions for thermostat connections.

Airflow Selector

Describes how to adjust airflow settings.

Dehumidification Method Selector

Explains selection of dehumidification modes.

Constant Torque Motors (ECM)

Options

Hot Gas Reheat (HGRH)

Explains the HGRH dehumidification option.

Electric Heat

Details on supplemental electric heat options.

Heat Recovery Package (HRP)

Description of the HRP for heating potable water.

Constant Airflow Motor

DPS Water Flow Proving

Pump Relay

Comfort Alert Module

Smart Start Assist

Mode of Operation

Explains operating modes and LED indications for SSA.

Heat Recovery Package

Water Tank Preparation

Steps for preparing the water tank for HRP connection.

Initial Start-Up

Sequence of Operation

Describes unit operation in cooling and heating modes.

Cooling Mode

Heating Mode

Application Considerations

Well Water Systems

Guidance for using well water with the heat pump.

Cooling Tower;Boiler Systems

Considerations for using cooling towers or boilers.

Geothermal Systems

System Checkout

Unit Start-Up

Procedures for starting the unit and verifying operation.

Maintenance

Unit Check-Out Sheet

Troubleshooting

UPM Board LED Indications

Interpreting LED blink codes for UPM board faults.

Unit Troubleshooting

Table of common problems, causes, and solutions.

Compressor Ohms

Comfort Alert Module - Flash Codes

HRP Troubleshooting

Smart Start Assist LED Status Indication

Electronic Thermostat

Operating Temperatures and Pressures

Airflow Tables

Constant Airflow Motor Airflow Table

Water Side Pressure Drop Table

Wiring Diagrams

Wiring Harness Drawings

Specific harness connection diagrams for motor types.

Spare Parts List

Vertical (VT)

Spare parts specific to Vertical configurations.

Horizontal (HZ)

Spare parts specific to Horizontal configurations.

Counter Flow

Spare parts specific to Counter Flow configurations.

Dimensional Drawings

Horizontal - Supply Air Configuration: End Blow

Dimensions for horizontal units with end blow supply air.

Horizontal - Straight Through

Dimensions for horizontal units with straight through supply air.

Horizontal - Hanging Bracket Location

Specifications for hanging bracket placement.

Counter Flow

Dimensions for Counter Flow units.

CF - Vertical

Dimensions for Counter Flow units in Vertical configuration.

Bosch SM036 Specifications

General IconGeneral
BrandBosch
ModelSM036
CategoryHeat Pump
LanguageEnglish

Related product manuals