EasyManua.ls Logo

Bosch WBN 6000-24 CR - Flue Gas Test; Setting Appliance Output; Tightness Test of the Flue Gas Path; Checking the CO Level in the Flue Gas

Bosch WBN 6000-24 CR
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Flue gas test
Gaz 6000 W – 6720866247 (2019/07)
32
13 Flue gas test
13.1 Setting appliance output
To set the maximum appliance output:
Select service function 1.2F and set operating mode 4
( Chapter 11.2, from page 27).
To set the minimum appliance output:
Select service function 1.2F and set operating mode 3
( Chapter 11.2, from page 27).
You have 15 minutes in which to take your measurements. After this time
the appliance returns to normal operation.
To set normal mode:
Select service function 1.2F and set operating mode 0
( Chapter 11.2, from page 27).
-or-
Press key .
The heating appliance returns to normal mode.
13.2 Tightness test of the flue gas path
Measuring O
2
or CO
2
levels in combustion air.
Use an annular gap probe for measuring.
With a type C
12
and C
32
flue gas routing system, the tightness of the flue
gas path can be tested by measuring the O
2
or CO
2
content of the
combustion air. The O
2
level must not be below 20,6 %. The CO
2
level
must not exceed 0,2 %.
Ensure heat transfer by opening the radiator valves or DHW tap.
Switch on the appliance and wait a few minutes.
Remove the plug from the combustion air test nipple [2].
Insert a flue gas probe into the connector and seal the test point.
Fig. 29 Flue gas test port and combustion air test nipple
[1] Flue gas test port
[2] Combustion air test nipple
Select service function 1.2F and set operating mode 4
( Chapter 11.2, from page 27).
▶Measure the CO
2
and O
2
levels.
Select service function 1.2F and set operating mode 0
( Chapter 11.2, from page 27) or key .
Switch off the appliance.
Remove the flue gas probe.
▶Replace the plug.
13.3 Checking the CO level in the flue gas
Use a multi-hole flue gas probe for the test.
Ensure heat transfer by opening the radiator valves or DHW tap.
Switch on the appliance and wait a few minutes.
Remove plug from flue gas test port ( Fig. 28, [1]).
Insert a flue gas probe as far as it will go into the port and seal the test
point.
Select service function 1.2F and set operating mode 4
( Chapter 11.2, from page 27).
Measure the CO content.
Select service function 1.2F and set operating mode 0
( Chapter 11.2, from page 27) or key .
Switch off the appliance.
Remove the flue gas probe.
Replace the plug.
13.4 Testing flue gas loss value
A flue gas probe and a temperature sensor are required for the test.
Ensure heat transfer by opening the radiator valves or DHW tap.
Switch on the appliance and wait a few minutes.
Remove the plug from the flue gas test port [1].
Insert flue gas probe approx. 60 mm into the connector and find the
position with the highest flue gas temperature.
Seal the test point.
Remove the plug from the combustion air test nipple [2].
Push the temperature sensor approx. 20 mm into the connector.
Seal the test point.
Select service function 1.2F and set operating mode 4
( Chapter 11.2, from page 27).
Test the flue gas loss value and combustion efficiency at a boiler
temperature of 60 °C.
Select service function 1.2F and set operating mode 0
( Chapter 11.2, from page 27) or key .
Switch off the appliance.
Remove the test probe.
Remove the temperature sensor.
Replace the plug.
FLUE
FLUE
0 010 005 985-001
21

Table of Contents

Other manuals for Bosch WBN 6000-24 CR

Related product manuals