17.3 Faults that are not shown on the display
Table 28 Faults that are not shown on the display
Appliance faults Remedy
Water circulation noises Correctly set the pump speed at the pump terminal box.
Heating up takes too long Correctly set the pump speed at the pump terminal box.
Flue gas readings incorrect;
CO content too high
Check gas type.
Check gas supply pressure and adjust if required.
Check flue system. Clean or repair if required.
Check gas settings; replace gas valve if required.
Ignition too violent, or poor Check gas type.
Check gas supply pressure and adjust if required.
Check power supply.
Check electrodes with cable. Replace if required.
Check flue system. Clean or repair if required.
Check gas settings; replace gas valve if required.
For natural gas: Check external gas flow monitor. Replace if required.
Check burner. Replace if required.
DHW outlet temperature is
not reached
Check appliance type and gas type; see service function 2.0A.
Check turbine. Replace if required.
No heating, no DHW (pump is not running) Unblock pump ( page 37).