Faults
Gaz 6000 W – 6720866247 (2019/07)
40
17.2 Faults that are shown on the display
Table 27
Display Description Remedy
A7 Hot water temperature sensor is faulty. Check the temperature sensor and connecting lead for breaks or short-
circuits and replace them if required ( page 37).
Ad Cylinder temperature sensor not detected. Check the cylinder temperature sensor and connecting lead, replace if
required.
C1 Fan speed too low. Check mains voltage.
Check the flue system and clean or repair if required.
C4 The differential pressure switch does not open when
fan switched off.
Check the differential pressure switch and cabling, also check the
connection hoses.
C6 Differential pressure switch does not close. Check the fan cable with plug and fan, replace if required.
Check the differential pressure switch and flue gas routing.
C7 Fan not running. Check the fan cable with plug and fan, replace if required.
CE Heating system charge pressure is too low. Top up the system with water.
d7 Gas valve is faulty. Check the connecting lead.
Check the gas valve and replace it if required.
E2 Flow temperature sensor is faulty (breaks). Check the temperature sensor and connecting lead for breaks or short
circuits, replace if required.
E9 Temperature limiter for heat exchanger has
responded.
Check the temperature limiter and connecting lead of the heat exchanger
for breaks, replace if required.
Check the operating pressure of the heating system.
Check the temperature limiter and replace if required.
Check the starting of the pump, replace pump if required.
Check the fuse and replace if required ( page 20).
Vent the device.
Check the heat exchanger on the water side and replace if required.
EA Flame not detected. Check that the earth lead is correctly connected.
Check whether the gas isolator is open.
Check the gas supply pressure and correct it if required.
Check the power supply.
Check the electrodes and cable, replace if required.
Check the flue system and clean or repair if required.
Check the gas setting and correct it if required.
For natural gas: Check the external gas flow monitor and replace it if
required.
In the case of open flue operation, check the interconnected room air
supply or ventilation openings.
Clean the heat exchanger ( page 36).
Check the gas valve and replace it if required.
Flame detected even when the burner is switched
off.
Check electrodes for contamination and replace if required.
Check the flue system and clean or repair if required.
Check the PCB for moisture and dry it if required.
FA After switching gas off: flame is detected. Check the gas valve and replace it if required.
Check the electrodes and connecting lead, replace if required.
Check the flue system and clean or repair if required.
Fd Key was held down for too long by mistake (over
30 secs.).
Press the key for 3 seconds.
P Appliance type not defined. Set the appliance type ( service function 3.1A).
Fan stage not set. Set the fan stage.