Type: Countdown, Repeat Countdown, Daily, Weekly or Monthly.
Countdown: Defines the interval of time, e.g. days, hours, minutes and
seconds.
(Not Real Time)
Repeat Countdown: Repeats the previous countdown. (Not Real Time)
Daily, Weekly or Monthly: The timer works in selected interval of Real Time.
Action: Disables or enables the timer.
Job1, Job2: 2 jobs can be configured for each timer.
4.3.1.1 Timer Example-1
Switch on water pump every day at 8.00 hrs and switch off at 10.00 hrs
This application requires to Daily type timer which works with Real Time Clock.
Configuration settings are as follows.
Timer1
Type: Daily Action: Enable
Time – Hour: 8 Min: 0 Sec: 0
Job1: DO Latch On, Target: DO1
Job2: No Action
Timer2
Type: Daily Action: Enable
Time – Hour: 10 Min: 0 Sec: 0
Job1: DO Latch Off, Target: DO1
Job2: No Action